Solar Engineering P2 Reference 5 min read Reviewed July 8, 2026 Nirav Dhanani Nirav Dhanani

Arc Fault

Arc faults in PV DC circuits are a fire risk. NEC 690.11 requires AFCI protection above 80 V. Detection technology and design implications.

Definition

An arc fault in a solar PV DC circuit is an unintended electric arc between conductors caused by loose connections, damaged insulation, or component failure. NEC 690.11 requires Arc-Fault Circuit Interrupter (AFCI) protection on DC circuits operating above 80 V.

NEC 690.11 Requirements

  • DC PV source and output circuits operating ≥ 80 V.
  • AFCI required on circuits “on or penetrating a building” (NEC 2017+).
  • Detection within seconds; disconnect within minutes (per UL 1699B).
  • Integrated AFCI in modern inverters typically satisfies the requirement.

Common Causes

  1. Loose MC4 connectors — most common.
  2. Damaged wire insulation (sun/water degradation).
  3. Corroded terminations.
  4. Damaged bypass diodes — see bypass diode activation for how this failure mode develops into a hot spot.
  5. Animal damage (rodent gnawing).

Prevention

  • Use manufacturer-listed MC4 crimp tools.
  • Inspect connections during commissioning.
  • Maintain conductor strain relief.
  • Use UL-listed combiner boxes and other listed components.
  • Periodic IR thermography surveys identify hot connections.

How AFCI Detection Works

Modern DC arc-fault circuit interrupters continuously sample the current waveform on each PV string for the broadband, high-frequency signature a real arc produces — a pattern distinct from the normal switching noise of an inverter or the ripple from cloud-driven current changes. When that signature crosses a validated threshold under UL 1699B, the AFCI logic confirms it isn’t a nuisance trip and opens only the affected string, rather than shutting down the whole array. That selective disconnection is why a single loose MC4 connector or a chafed conductor can be isolated without derating the rest of the plant. Because integrated AFCI now ships inside most string inverters, the practical design task for an EPC is less about specifying a separate device and more about confirming the inverter’s AFCI is listed for the operating voltage and correctly annotated in the solar SLD software or electrical drawing package, so the protection boundary is visible to permit reviewers.

Key Takeaways

  • Arc fault = unintended electric arc between PV conductors; fire risk.
  • NEC 690.11 requires AFCI protection on DC circuits ≥ 80 V.
  • Modern string inverters include integrated AFCI per UL 1699B.
  • Most common cause: improper MC4 connector termination.
  • Prevent via proper crimping, periodic IR thermography.

Arc-fault protection rarely gets specified in isolation — it shows up on the same drawing set as the DC and AC electrical layout our Electrical CEIG Drawings service produces, where AFCI, ground-fault, and rapid-shutdown devices all have to be called out for the permit reviewer. If a string keeps tripping after AFCI has ruled out an obvious wiring fault, the root cause is often on the inverter side rather than the DC circuit itself; QbitsEnergy’s inverter troubleshooting guide is a useful next step for isolating that class of fault. Teams assembling the full DC protection scheme — AFCI, combiner sizing, and grounding together — will also find the Ground Fault entry useful, since the two failure modes are detected separately but are frequently confused during commissioning walk-throughs.

Frequently Asked Questions

6 commonly searched questions about Arc Fault.

What is an arc fault?
An unintended electric arc between conductors in a PV circuit. Causes: loose MC4 connector, degraded wire, corroded terminal, damaged module bypass diode. Generates heat and can ignite surrounding materials.
What does AFCI detect?
High-frequency current signatures characteristic of arc faults. Modern inverters with integrated AFCI continuously monitor for these signatures and disconnect the affected string.
Is AFCI required?
Yes per NEC 690.11 for DC circuits operating ≥80 V on or penetrating buildings. Most modern inverters include integrated DC AFCI.
Difference between arc fault and ground fault?
Arc fault: arc between conductors (not necessarily to ground). Ground fault: unintended current path to ground/earth. Both detected separately; both required by NEC.
Common arc fault causes?
Loose or improperly crimped MC4 connectors (most common), damaged wire insulation, water-corroded terminations, module hot-spot escalation.
What happens when AFCI trips?
Inverter disconnects the affected string and signals an alert. System remains offline until manual reset after the cause is identified and corrected.

Need engineering-backed solar designs?

Heaven Designs delivers PE-stamped solar design packages, structural calculations, electrical engineering, and utility-compliant permit plans.