Voc (open-circuit voltage) is the voltage across a PV module's terminals when no current flows, the highest voltage it produces. It is rated at Standard Test Conditions of 1,000 W/m2, 25 °C cell temperature, and AM 1.5 spectrum per IEC 60904, and it controls maximum string length under NEC 2023 690.7.
Quick Facts
| Field | Detail |
|---|---|
| Term | Voc, Open-Circuit Voltage |
| Category | Solar Engineering |
| Engineering Discipline | Electrical Design, String Sizing |
| Standard | IEC 60904 |
| Typical Range | 38-50 V (commercial PV modules) |
| Difficulty Level | Beginner to Intermediate |
What is Voc?
Voc is the voltage across a PV module’s terminals when the circuit is open (no current flows). It is one of the four characteristic points on the module’s I-V curve, along with Vmp, Imp, and Isc.
Relationship to I-V Curve
- Isc at V = 0 (terminals shorted).
- Voc at I = 0 (open circuit).
- Pmax at Vmp × Imp.
- Voc > Vmp; Isc > Imp.
All four values are read at STC off the module datasheet, and all four shift together once the array is running under real irradiance and cell temperature.
Temperature Dependence
Voc(T) = Voc(STC) × [1 + β_Voc × (T − 25°C)]
- β_Voc, the temperature coefficient of Voc: typically −0.0025 to −0.0030 /°C (datasheet value).
- T: cell temperature (use site ambient for cold-day calculation; cell temperature is approx. ambient for no-load conditions).
Cold temperature effect
At −10°C: Voc increases ~9% over STC. At −20°C: Voc increases ~13.5% over STC.
Hot temperature effect
At 65°C: Voc decreases ~12% from STC. At 80°C: Voc decreases ~16.5% from STC.
Worked Example
Module Voc(STC) = 41.6 V, β_Voc = −0.27 %/°C.
Site: Boston, MA. ASHRAE 99.6% min = −18°C.
Voc(−18°C) = 41.6 × [1 + (−0.0027)(−18 − 25)]
= 41.6 × [1 + 0.1161]
= 41.6 × 1.1161
= 46.4 V per module
For NEC 690.7 limit 1,000 V: floor(1000 / 46.4) = 21 modules max in series. This cold-day Voc figure is the input every string sizing calculation starts from, get it wrong and the rest of the string count follows it off a cliff.
Engineering Considerations
- Always use site-specific ASHRAE extreme low: not annual average.
- β_Voc must come from manufacturer datasheet; varies by cell technology.
- TOPCon and HJT modules have tighter (less negative) β_Voc, allowing slightly longer strings in cold climates.
- Cable voltage drop doesn’t apply to Voc check (no current at open circuit).
- Bifacial modules can have slightly higher Voc due to rear-side irradiance effects.
Common Mistakes
- Using STC Voc without temperature correction.
- Using annual average minimum instead of extreme low.
- Forgetting to apply β_Voc as negative when cold.
- Mixing modules with different Voc on the same string.
Best Practices
- Document the cold-day Voc calculation directly on the SLD, most solar SLD software with NEC auto-generation will flag a string that violates 690.7 before the drawing goes out for permit.
- Cite the ASHRAE table or local code for the cold temperature used.
- Cross-check string sizing software output against the manual formula.
- Design string Voc to 90% of NEC limit for thermal and measurement margin.
Related Reading
The Voc number on a datasheet only becomes real once it’s checked against hardware limits and confirmed in the field. On the inverter side, the maximum DC input voltage rating that a string design must respect traces back to IEC 62109 inverter safety standard, which governs how that ceiling is set and tested.
During commissioning, technicians re-measure open-circuit voltage on every string as part of the solar inverter commissioning protocol to confirm the design-stage Voc calculation held up against as-built conditions. Readers who want the string sizing math laid out end-to-end, from Voc through NEC 690.7 to final module count, can also see it walked through in Qbits Energy’s string sizing glossary entry.
Standards & Certifications
- IEC 60904, STC measurement procedure.
- IEC 61215, Crystalline module qualification.
- NEC 690.7, Maximum system voltage compliance.
Key Takeaways
- Voc is the open-circuit voltage of a PV module at STC; the controlling parameter for NEC 690.7 string sizing.
- Voc rises with falling temperature (typical β = −0.25 to −0.30 %/°C).
- Always temperature-correct using site-specific extreme low (ASHRAE or local code).
- Design to 90% of the NEC limit for safety margin.
- The cold-day Voc calculation must appear on the SLD.
Disclosure: Qbits Energy is a Heaven Designs group company.
Frequently Asked Questions
3 commonly searched questions about Voc (Open-Circuit Voltage).
What is the difference between Voc and Vmp?
How do you correct Voc for cold temperatures?
Why is Voc important for safety?
Need engineering-backed solar designs?
Heaven Designs prepares solar drawings, structural calculations, electrical engineering documents, and project-specific permit plan sets.
Keyur Rakholiya