Open-Circuit Voltage (Voc) is the maximum voltage a PV module produces when no load is connected, measured at Standard Test Conditions. It is the controlling parameter for string sizing against NEC 690.7 maximum system voltage.
Quick Facts
| Field | Detail |
|---|---|
| Term | Voc — Open-Circuit Voltage |
| Category | Solar Engineering |
| Engineering Discipline | Electrical Design, String Sizing |
| Standard | IEC 60904 |
| Typical Range | 38–50 V (commercial PV modules) |
| Difficulty Level | Beginner to Intermediate |
What is Voc?
Voc is the voltage across a PV module’s terminals when the circuit is open (no current flows). It is one of the four characteristic points on the module’s I-V curve, along with Vmp, Imp, and Isc.
Relationship to I-V Curve
- Isc at V = 0 (terminals shorted).
- Voc at I = 0 (open circuit).
- Pmax at Vmp × Imp.
- Voc > Vmp; Isc > Imp.
All four values are read at STC off the module datasheet, and all four shift together once the array is running under real irradiance and cell temperature.
Temperature Dependence
Voc(T) = Voc(STC) × [1 + β_Voc × (T − 25°C)]
- β_Voc, the temperature coefficient of Voc: typically −0.0025 to −0.0030 /°C (datasheet value).
- T: cell temperature (use site ambient for cold-day calculation; cell temperature is approx. ambient for no-load conditions).
Cold temperature effect
At −10°C: Voc increases ~9% over STC. At −20°C: Voc increases ~13.5% over STC.
Hot temperature effect
At 65°C: Voc decreases ~12% from STC. At 80°C: Voc decreases ~16.5% from STC.
Worked Example
Module Voc(STC) = 41.6 V, β_Voc = −0.27 %/°C.
Site: Boston, MA. ASHRAE 99.6% min = −18°C.
Voc(−18°C) = 41.6 × [1 + (−0.0027)(−18 − 25)]
= 41.6 × [1 + 0.1161]
= 41.6 × 1.1161
= 46.4 V per module
For NEC 690.7 limit 1,000 V: floor(1000 / 46.4) = 21 modules max in series. This cold-day Voc figure is the input every string sizing calculation starts from — get it wrong and the rest of the string count follows it off a cliff.
Engineering Considerations
- Always use site-specific ASHRAE extreme low, not annual average.
- β_Voc must come from manufacturer datasheet; varies by cell technology.
- TOPCon and HJT modules have tighter (less negative) β_Voc, allowing slightly longer strings in cold climates.
- Cable voltage drop doesn’t apply to Voc check (no current at open circuit).
- Bifacial modules can have slightly higher Voc due to rear-side irradiance effects.
Common Mistakes
- Using STC Voc without temperature correction.
- Using annual average minimum instead of extreme low.
- Forgetting to apply β_Voc as negative when cold.
- Mixing modules with different Voc on the same string.
Best Practices
- Document the cold-day Voc calculation directly on the SLD — most solar SLD software with NEC auto-generation will flag a string that violates 690.7 before the drawing goes out for permit.
- Cite the ASHRAE table or local code for the cold temperature used.
- Cross-check string sizing software output against the manual formula.
- Design string Voc to 90% of NEC limit for thermal and measurement margin.
Related Reading
The Voc number on a datasheet only becomes real once it’s checked against hardware limits and confirmed in the field. On the inverter side, the maximum DC input voltage rating that a string design must respect traces back to IEC 62109 inverter safety standard, which governs how that ceiling is set and tested. During commissioning, technicians re-measure open-circuit voltage on every string as part of the solar inverter commissioning protocol to confirm the design-stage Voc calculation held up against as-built conditions. Readers who want the string sizing math laid out end-to-end, from Voc through NEC 690.7 to final module count, can also see it walked through in qbitsenergy’s string sizing glossary entry.
Standards & Certifications
- IEC 60904 — STC measurement procedure.
- IEC 61215 — Crystalline module qualification.
- NEC 690.7 — Maximum system voltage compliance.
Key Takeaways
- Voc is the open-circuit voltage of a PV module at STC; the controlling parameter for NEC 690.7 string sizing.
- Voc rises with falling temperature (typical β = −0.25 to −0.30 %/°C).
- Always temperature-correct using site-specific extreme low (ASHRAE or local code).
- Design to 90% of the NEC limit for safety margin.
- The cold-day Voc calculation must appear on the SLD.
Frequently Asked Questions
9 commonly searched questions about Voc (Open-Circuit Voltage).
What is Voc?
Why is Voc important for string sizing?
How does Voc change with temperature?
What's the formula for Voc at temperature?
How is Voc different from Vmp?
Does Voc vary by module type?
What happens if string Voc exceeds NEC limit?
Does Voc decrease over module lifetime?
Is Voc checked again after installation?
Need engineering-backed solar designs?
Heaven Designs delivers PE-stamped solar design packages, structural calculations, electrical engineering, and utility-compliant permit plans.
Keyur Rakholiya