Solar Engineering P3 Reference 3 min read Reviewed July 8, 2026 Nimesh Katariya Nimesh Katariya

EGC (Equipment Grounding Conductor)

NEC 250.122 sets equipment grounding conductor (EGC) size by OCPD rating. Use the 250.122 table for copper and aluminum EGCs and see how NEC 690.45 applies.

Quick answer

An EGC (equipment grounding conductor) bonds exposed metal parts such as module frames, racking, enclosures and conduit back to the source, giving fault current a low-impedance path so the overcurrent device trips. NEC 250.122 sizes the EGC from the rating of the upstream OCPD, and NEC 2023 Section 690.45 applies that same table to PV circuits.

NEC 250.122 is the table that sets equipment grounding conductor (EGC) size, and it is the rule solar permit designers and electricians apply on every PV circuit. This entry explains what an EGC does, gives the 250.122 sizing table, and shows how NEC 690.45 applies it to solar arrays.

What is an EGC in electrical and solar systems?

The Equipment Grounding Conductor is a dedicated bonding conductor, not a current-carrying conductor under normal operation. Every metallic part of the system that a technician could touch, module frames, racking rails, combiner box enclosures, conduit, and inverter chassis, gets bonded to it.

If an ungrounded conductor ever faults to a metal frame or enclosure, the EGC gives that fault current a deliberately low-impedance path back to the source, which is what allows the overcurrent protective device (OCPD) to trip fast instead of leaving the equipment “live” at a dangerous touch voltage.

This is why EGC sizing under NEC 250.122 is driven by the OCPD rating rather than by the load current the circuit normally carries, and why it sits alongside the broader grounding, bonding, and overcurrent requirements laid out across NEC 690 for grid-tied PV systems, the conductor only needs to survive briefly during a fault, not carry continuous current.

Worked Example

A rooftop PV source circuit is protected by a 20 A breaker at the combiner box.

Per the NEC 250.122 table above, the minimum copper EGC for a 20 A OCPD is 12 AWG. NEC 690.45 points PV circuits back to the same table. Where a PV circuit has no overcurrent device, the designer sizes the EGC from an assumed OCPD rating per 690.9(B).

NEC 250.122 table: EGC size by OCPD rating

OCPD (A)Copper EGCAluminum EGC
1514 AWG12 AWG
2012 AWG10 AWG
30-6010 AWG8 AWG
1008 AWG6 AWG
2006 AWG4 AWG
4003 AWG1 AWG

Key Takeaways

  • EGC = safety grounding conductor.
  • Sized per NEC 250.122 by OCPD rating.
  • Bonds all metallic equipment to ground.
  • NEC 690.45 applies Table 250.122 to PV circuits, using an assumed OCPD where none exists.
  • Upsizing the EGC for voltage drop is not required on PV circuits.

EGC sizing rarely gets calculated in isolation, it sits next to conductor ampacity and conduit fill as one more line item on the same circuit schedule, since a designer has to confirm the current-carrying conductors, their derated ampacity, and the bonding conductor all fit correctly within the same raceway.

On drawing sets, the EGC callout shows up directly on the one-line: our breakdown of solar SLD software and NEC 2023 auto-generation walks through how these grounding and bonding annotations get pulled onto the single-line diagram automatically rather than hand-drafted circuit by circuit.

For projects where the EGC path runs through ground-mounted racking and piers rather than a rooftop, it’s worth cross-checking against the structural side too, see our pile foundation design guide for solar ground-mount for how grounding and structural bonding points interact on that racking type.

Frequently Asked Questions

4 commonly searched questions about EGC (Equipment Grounding Conductor).

How do you size an EGC per NEC 250.122?
Find the rating of the overcurrent device ahead of the circuit, then read the minimum EGC size from Table 250.122. For copper, 15 A needs 14 AWG, 20 A needs 12 AWG, 60 A needs 10 AWG and 100 A needs 8 AWG. Larger sizes follow the same table.
How is the EGC sized on a PV circuit with no fuse?
NEC 690.45 still uses Table 250.122. Where a PV circuit has no overcurrent device, the designer assumes an OCPD sized per 690.9(B) from the circuit's maximum current and reads the EGC size from that assumed rating. Upsizing for voltage drop is not required.
Is the EGC the same as the grounding electrode conductor (GEC)?
No. The EGC bonds equipment so a fault clears quickly through the OCPD. The GEC connects the grounding electrode system, such as ground rods or a concrete-encased electrode, to the service or system. Both belong to the grounding and bonding system but do different jobs.
Can the EGC run in the same conduit as the circuit conductors?
Yes, and it normally should. Running the EGC in the same raceway or cable as the circuit conductors keeps the fault path short and its impedance low. That helps the overcurrent device clear a ground fault quickly instead of leaving metal parts energized.

Need engineering-backed solar designs?

Heaven Designs prepares solar drawings, structural calculations, electrical engineering documents, and project-specific permit plan sets.

Ready for constructible design packages?

Solar engineering for EPCs. MEP design and BIM for AEC teams. Reply within 1 business day.

Get a quote WhatsApp