Solar Engineering P2 Reference 3 min read Reviewed July 8, 2026 Nimesh Katariya Nimesh Katariya

OCPD (Overcurrent Protection Device)

OCPD is a fuse or breaker protecting solar PV conductors. NEC 690.9 sizing at 1.25 × Isc.

Definition

Overcurrent Protection Device (OCPD) is a fuse or circuit breaker that interrupts current flow when it exceeds a safe threshold. NEC 690.9 sizes OCPD at 1.25 × Isc for PV source circuits.

NEC 690.9 Sizing

OCPD_minimum = 1.25 × Isc (rounded up to standard)

Standard OCPD Ratings

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400 A.

Why the 1.25× Factor

The 125% multiplier in NEC 690.9 is not an arbitrary safety margin — it accounts for two effects that stack on top of each other. First, a module’s short-circuit current under real-world high-irradiance conditions can run above its STC nameplate Isc, so a fuse sized to the exact datasheet value would be prone to nuisance trips on a clear, cold, high-sun day. Second, NEC 690.8 already limits continuous-duty conductors to 80% of their rated ampacity, and 1 ÷ 0.8 works out to the same 1.25 factor from the wire side of the calculation. Sizing the OCPD at 1.25 × Isc keeps the fuse or breaker comfortably above expected operating current while still tripping fast enough to protect the conductor if a real fault develops.

Worked Example

A module datasheet lists Isc = 10.8 A. Applying NEC 690.9: 1.25 × 10.8 A = 13.5 A. Since 13.5 A isn’t a standard rating, the design rounds up to the next standard OCPD size — 15 A. If two or more strings are paralleled into a combiner box ahead of that point, each string typically needs its own fuse at this same rating, since parallel strings can otherwise backfeed fault current into one another during a short circuit.

Key Takeaways

  • OCPD = fuse or breaker, NEC 690.9 sized at 1.25 × Isc.
  • Source-circuit: typically gPV fuse in combiner.
  • Inverter output: AC breaker.
  • Each parallel string > 2 needs individual fuse.
  • Round up to standard rating.

OCPD sizing is one line item in a much larger DC electrical package — the fuse or breaker rating, its placement in the combiner box, and its relationship to conductor ampacity all need to show up correctly on the drawing set, which is exactly what our Electrical CEIG Drawings service documents for permit review, alongside the Solar SLD software workflows EPCs increasingly use to auto-generate that same NEC 2023 protection scheme. Overcurrent protection is closely tied to how conductors and strings are sized in the first place; QbitsEnergy’s guide to string sizing and overcurrent protection walks through that upstream calculation in more depth. For the other DC protection device that gets specified alongside OCPD on the same circuits, see Arc Fault — the two are sized and tested independently, but both end up on the same combiner-box schedule.

Frequently Asked Questions

6 commonly searched questions about OCPD (Overcurrent Protection Device).

What is an OCPD?
Overcurrent Protection Device — fuse or circuit breaker protecting circuit conductors from overcurrent. For PV source circuits, NEC 690.9 sizes OCPD at 1.25 × Isc.
What's the standard fuse size?
Round up to next standard rating: 15, 20, 25, 30, 35, 40 A. For Isc = 13.5 A: 1.25 × 13.5 = 17 A → 20 A standard.
Fuse or breaker?
PV source-circuit: typically gPV-rated fuse in combiner. Inverter output: typically AC breaker in service panel.
Does each parallel string need its own fuse?
Yes per NEC 690.9 if 2+ strings parallel without overcurrent protection elsewhere.
Does an OCPD also protect against ground faults or arc faults?
No. An OCPD only interrupts current that exceeds its rated overcurrent threshold. Ground faults and arc faults are separate failure modes detected by dedicated devices — a ground-fault protection device and an AFCI — that operate alongside, not instead of, the OCPD.
Why is OCPD sized at 1.25× Isc instead of exactly matching it?
The 125% factor in NEC 690.9 builds in margin for two things at once: PV modules can produce short-circuit current above their nameplate rating under high irradiance, and continuous-duty conductors are only rated to carry 80% of their ampacity per NEC 690.8, which works out to the same 1.25× multiplier from the other direction. Sizing the fuse or breaker exactly at Isc would risk nuisance trips on a sunny, high-irradiance day.

Need engineering-backed solar designs?

Heaven Designs delivers PE-stamped solar design packages, structural calculations, electrical engineering, and utility-compliant permit plans.