Wire sizing for solar PV systems determines conductor type, AWG/kcmil size, and length to safely carry the maximum circuit current under NEC 690.8, with acceptable voltage drop (typically ≤ 2–3%) and temperature/conduit-fill derating.
Quick Facts
| Field | Detail |
|---|---|
| Term | Wire Sizing |
| Category | Solar Engineering |
| Engineering Discipline | Electrical Design |
| Relevant Codes | NEC 690.8, NEC 215, NEC 310 |
| Software | Bluebeam plugins, Excel, NREL Wire Sizer |
| Difficulty Level | Intermediate |
Wire Sizing Workflow
Step 1: Calculate maximum circuit current
I_circuit_max = 1.25 × Isc (NEC 690.8(A))
I_for_conductor = 1.25 × I_circuit_max = 1.5625 × Isc (NEC 690.8(B))
Step 2: Pick conductor type
- PV Wire: source circuits exposed outdoors.
- USE-2: source/output, direct burial OK.
- THHN/THWN-2: AC interior runs.
- XHHW-2: hot environments.
Step 3: Look up base ampacity (NEC Table 310.16, 90°C column)
Step 4: Apply temperature derating (NEC Table 310.15(B)(2)(a))
Step 5: Apply conduit fill derating (NEC Table 310.15(B)(3)(a))
Step 6: Verify derated ampacity ≥ I_for_conductor
Step 7: Calculate voltage drop, upsize if > 2–3%
Worked Example
Project: 18-module string, Isc = 13.5 A.
- I_for_conductor = 1.5625 × 13.5 = 21.1 A.
- Ambient: 50°C. Conduit fill: 4 conductors.
- Use 10 AWG PV Wire (base ampacity 40 A at 90°C).
- Temp derate (50°C): × 0.82 = 32.8 A.
- Conduit derate (4 conductors): × 0.80 = 26.3 A.
- 26.3 A > 21.1 A → ✓ adequate.
Voltage drop check (round-trip 100 ft, R for 10 AWG = 1.0 ohm/kft):
Vd = 2 × 13.5 × 100 × 1.0 / 1000 = 2.7 V
Vd % = 2.7 / 600 = 0.45% → ✓ acceptable
NEC Ampacity Tables (90°C insulation)
| AWG/kcmil | Ampacity (90°C, NEC 310.16) |
|---|---|
| 14 | 30 A |
| 12 | 40 A |
| 10 | 55 A |
| 8 | 75 A |
| 6 | 105 A |
| 4 | 140 A |
| 2 | 190 A |
| 1/0 | 260 A |
| 4/0 | 405 A |
| 250 kcmil | 455 A |
Note: Final ampacity after derating per NEC 240.4 may not exceed 60°C or 75°C ampacity columns depending on terminal ratings.
EGC Sizing (NEC 250.122)
| OCPD (A) | Copper EGC (AWG) |
|---|---|
| 15 | 14 |
| 20 | 12 |
| 30–60 | 10 |
| 100 | 8 |
| 200 | 6 |
| 400 | 3 |
Common Mistakes
- Using Imp instead of Isc.
- Forgetting double 1.25 multiplier in 690.8.
- Skipping temperature derating.
- Ignoring conduit fill effect.
- Voltage drop too high — undersizing for long runs.
- EGC undersized.
Best Practices
- Show all derating calculations on the SLD.
- Use 90°C conductors (PV Wire, XHHW-2) for ampacity headroom.
- Target ≤ 2% DC voltage drop, ≤ 1% AC voltage drop.
- For long runs, increase string voltage rather than upsize wire.
- Verify terminal temperature rating limits final ampacity.
Standards & Certifications
- NEC 690.8 — Solar conductor sizing.
- NEC 310 — Conductor properties and derating tables.
- NEC 250.122 — EGC sizing.
- UL 4703 — PV Wire listing.
- UL 854 — USE-2 listing.
Key Takeaways
- Wire sizing per NEC 690.8: 1.25 × Isc × 1.25 = 1.5625 × Isc minimum ampacity.
- Apply temperature and conduit-fill derating from NEC Table 310.15.
- Voltage drop ≤ 2% DC, ≤ 1% AC industry target.
- Use PV Wire outdoors, THHN-2 indoors, USE-2 underground.
- EGC sized per NEC 250.122 based on OCPD rating.
Frequently Asked Questions
10 commonly searched questions about Wire Sizing.
How do I size PV wire?
What conductor types are used in solar PV?
What is voltage drop limit?
How do I calculate voltage drop?
What's the difference between PV Wire and USE-2?
How does temperature derating work?
What is conduit fill derating?
Can I use 12 AWG PV Wire on most residential systems?
How long is too long for a PV wire run?
Do I need separate ground conductors?
Need engineering-backed solar designs?
Heaven Designs delivers PE-stamped solar design packages, structural calculations, electrical engineering, and utility-compliant permit plans.