Solar Engineering P1 Reference 7 min read Reviewed July 8, 2026 Nimesh Katariya Nimesh Katariya

Wire Sizing

Solar wire sizing under NEC 690.8 covers ampacity, temperature derating and voltage drop. Learn how to pick conductor type, AWG size and conduit fill.

Quick answer

Wire sizing is selecting a conductor's material, insulation, and cross-section so it carries the circuit's current safely with acceptable voltage drop. For US PV source circuits, NEC 2023 690.8 typically applies 125% of Isc and another 125% continuous-duty factor, a combined 156%, before ampacity corrections from Table 310.16.

Quick Facts

FieldDetail
TermWire Sizing
CategorySolar Engineering
Engineering DisciplineElectrical Design
Relevant CodesNEC 690.8, NEC 215, NEC 310
SoftwareBluebeam plugins, Excel, NREL Wire Sizer
Difficulty LevelIntermediate

Wire Sizing Workflow

Step 1: Calculate maximum circuit current

I_circuit_max = 1.25 × Isc (NEC 690.8(A))
I_for_conductor = 1.25 × I_circuit_max = 1.5625 × Isc (NEC 690.8(B))

Step 2: Pick conductor type

  • PV Wire: source circuits exposed outdoors.
  • USE-2: source/output, direct burial OK.
  • THHN/THWN-2: AC interior runs.
  • XHHW-2: hot environments.

Source circuit conductors usually terminate at a combiner box, where string-level OCPD and grounding are consolidated before the feeder run to the inverter, the conductor type and ampacity selected here should match what the combiner box’s terminals are rated for.

Step 3: Look up base ampacity (NEC Table 310.16, 90°C column)

Step 4: Apply temperature derating (NEC Table 310.15(B)(2)(a))

Step 5: Apply conduit fill derating (NEC Table 310.15(B)(3)(a))

Step 6: Verify derated ampacity ≥ I_for_conductor

Step 7: Calculate voltage drop, upsize if > 2-3%

Worked Example

Project: 18-module string, Isc = 13.5 A.

  • I_for_conductor = 1.5625 × 13.5 = 21.1 A.
  • Ambient: 50°C. Conduit fill: 4 conductors.
  • Use 10 AWG PV Wire (base ampacity 40 A at 90°C).
  • Temp derate (50°C): × 0.82 = 32.8 A.
  • Conduit derate (4 conductors): × 0.80 = 26.3 A.
  • 26.3 A > 21.1 A → ✓ adequate.

Voltage drop check (round-trip 100 ft, R for 10 AWG = 1.0 ohm/kft):

Vd = 2 × 13.5 × 100 × 1.0 / 1000 = 2.7 V
Vd % = 2.7 / 600 = 0.45% → ✓ acceptable

NEC Ampacity Tables (90°C insulation)

AWG/kcmilAmpacity (90°C, NEC 310.16)
1430 A
1240 A
1055 A
875 A
6105 A
4140 A
2190 A
1/0260 A
4/0405 A
250 kcmil455 A

Note: Final ampacity after derating per NEC 240.4 may not exceed 60°C or 75°C ampacity columns depending on terminal ratings.

EGC Sizing (NEC 250.122)

OCPD (A)Copper EGC (AWG)
1514
2012
30-6010
1008
2006
4003

Common Mistakes

  1. Using Imp instead of Isc.
  2. Forgetting double 1.25 multiplier in 690.8.
  3. Skipping temperature derating.
  4. Ignoring conduit fill effect.
  5. Voltage drop too high, undersizing for long runs.
  6. EGC undersized.

Best Practices

  • Show all derating calculations on the SLD.
  • Use 90°C conductors (PV Wire, XHHW-2) for ampacity headroom.
  • Target ≤ 2% DC voltage drop, ≤ 1% AC voltage drop.
  • For long runs, increase string voltage rather than upsize wire.
  • Verify terminal temperature rating limits final ampacity.

Standards & Certifications

  • NEC 690.8, Solar conductor sizing.
  • NEC 310, Conductor properties and derating tables.
  • NEC 250.122, EGC sizing.
  • UL 4703, PV Wire listing.
  • UL 854, USE-2 listing.

Key Takeaways

  • Wire sizing per NEC 690.8: 1.25 × Isc × 1.25 = 1.5625 × Isc minimum ampacity.
  • Apply temperature and conduit-fill derating from NEC Table 310.15.
  • Voltage drop ≤ 2% DC, ≤ 1% AC industry target.
  • Use PV Wire outdoors, THHN-2 indoors, USE-2 underground.
  • EGC sized per NEC 250.122 based on OCPD rating.

Wire sizing doesn’t happen in isolation, the Isc figure feeding the 1.5625 multiplier comes out of string sizing decisions made earlier in the design, and the derated ampacity and voltage-drop results feed straight into the single-line diagram and cable schedule.

Qbitsenergy’s string sizing glossary entry walks through how that upstream Isc/Voc figure gets set, and its AC cable sizing reference covers the inverter-to-panel side of the run that this entry doesn’t.

On the documentation side, Heaven Designs’ guide to solar SLD software explains how leading platforms auto-generate conductor schedules and derating calculations once these numbers are locked in, and SurgePV’s single-line diagram software comparison is a useful companion for evaluating tools built around that workflow.

Wire sizing combines conductor ampacity, voltage drop and OCPD rating checks, and conductor type follows the PV Wire vs USE-2 rules.

Disclosure: Qbits Energy and SurgePV are Heaven Designs group companies.

Frequently Asked Questions

3 commonly searched questions about Wire Sizing.

Why do solar conductors use 156% of short-circuit current?
The first 125% factor accounts for irradiance above standard test conditions, which raises module current. The second 125% factor treats PV as a continuous load. Multiplying them gives 1.56 times Isc as the minimum conductor ampacity for most PV source circuits.
What corrections apply to wire ampacity in solar systems?
Designers correct for ambient temperature, including rooftop heat gain where it applies, and for the number of current-carrying conductors in a raceway. The corrected ampacity must still meet the circuit's required current, and termination temperature ratings also limit the result.
How is wire sizing done in India?
Indian designers commonly follow IS 732 for wiring practice and IEC 62548 or the cable maker's current ratings for PV DC cables, applying derating for temperature and grouping. Cables are often checked for voltage drop and short-circuit withstand as well as continuous current.

Need engineering-backed solar designs?

Heaven Designs prepares solar drawings, structural calculations, electrical engineering documents, and project-specific permit plan sets.

Ready for constructible design packages?

Solar engineering for EPCs. MEP design and BIM for AEC teams. Reply within 1 business day.

Get a quote WhatsApp